8.1.2. Cooling Operation
8.1.2.1. Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
8.1.3. Soft Dry Operation
8.1.3.1. Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
8.1.4. Heating Operation
8.1.4.1. Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF
point.